Sensor Connection Status; Sensor Pv Display - Honeywell XYR 6000 User Manual

Onewireless wcx series wireless valve position sensor
Hide thumbs Also See for XYR 6000:
Table of Contents

Advertisement

5.2

Sensor Connection Status

Displayed
Definition
status
NO KEY
Sensor needs a key from the Authentication
Device and is not transmitting.
NOT CONN
Sensor is in between discovery attempts.
DISCOVER
Sensor has not made a connection to a
Multinode and is in discovery (searching for a
connection to a Multinode). Sensor will
automatically enter a power saving mode if it
cannot make a connection and will retry later.
SECURING
Sensor has connected with the network and
is validating its key.
CONNECTD
Sensor has validated the key and has made
a secure connection with at least two
Multinodes. Sensor should appear in
Wireless Builder as an uncommissioned
device.
NO REDUN
No redundancy, that is, Sensor has
connected with only one Multinode.
5.3

Sensor PV Display

In PV display, the following information is displayed in sequence.
Item displayed
Channel number
Revision 1
OneWireless XYR 6000 Wireless Valve Position Sensor User's Manual
1/15/09
Table 7 WCX Sensor Connection Status
Example
1
5.2. Sensor Connection Status
What to do
Transmit a key to the sensor. See page 30.
If Sensor does not make a connection within
five minutes, do the following:
Check that Key is correct for the network
you are trying to join.
Check that Multinode(s) in the local area
are turned on and are already a secure
part of the network.
Check if KeyServer is active.
Check the KeyServer Event Log to see if
the Sensor is actively trying to join.
Errors in the Event Log show that the
Sensor is trying to join but that there are
problems. Consult the OneWireless
Wireless Builder documentation for
troubleshooting errors.
Wait for connection. If Sensor does not
make a connection within five minutes, see
NOT CONN in this table.
Wait for connection. If Sensor does not
make a connection within five minutes, see
NOT CONN in this table.
No action required.
No action required. The Sensor will
periodically look for a second Multinode in
order to form a redundant connection to the
network
Details
Channel number.
5. 4BOperation
23

Advertisement

Table of Contents
loading

Table of Contents