Igniter Location - Rheem 96P series Installation Instructions Manual

4 position condensing two-stage psc gas furnaces
Hide thumbs Also See for 96P series:
Table of Contents

Advertisement

The igniter location is critical to furnace operation.
If the igniter is ever replaced always pay attention to the
electrodes of the igniter to verify they are properly gapped.
The gap should be .110" (2.79mm) between the elec-
trodes.
FIGURE 52
ENSURE THE ELECTRODE GAP IS LOCATED IN THE HATCHED
AREA RELATIVE TO THE BURNER FACE.
IDEAL LOCATION
.000
.052
.173
.068
.000
ST-A1194-105-00
ST-A1194-105
FIGURE 54
SPARK GAP BETWEEN IGNITER ELECTRODES
Once the gap is properly verified and installed the location
of the gap must be in the proper location in relation to the
burner for best performance. See Figure 52 for igniter lo-
cation.
FIGURE 53
IGNITER ELECTRODE TO THE BURNER FACE
.151
.110 ± .015
SPARK GAP
ST-A1194-107
+ .060
.213
- .030
ST-A1194-106
ST-A1194-106
109