Ramps Adjustment - Omron 3G3JX Quick Start Manual

200 v class three-phase input 0.2 to 7.5 kw; 200 v class single-phase input 0.2 to 2.2 kw; 400 v class three-phase input 0.4 to 7.5 kw
Hide thumbs Also See for 3G3JX:
Table of Contents

Advertisement

PROGRAMMING JX
Select Run command source on parameter A002
Parameter
Adjust the stopping method by b091 and the acceleration/deceleration ramps on parameters F002 and F003
Parameter
Set the motor base frequency and AVR voltage of the motors in parameters A003 and A082
Parameter
Set the motor data: rated current (b012), rated power (H003) and number of poles (H004)
Parameter
At this point the inverter is ready to run the motor for the first time, but first review this check-list:
Verify the power LED is ON. If not, check the power connections.
Make sure the motor is disconnected from any mechanical load.
Make sure that you have a frequency reference checking the content of F001.
Now give the RUN command from the selected source. The RUN LED will turn ON.
The motor should start turning.
Remove the RUN command or press the STOP key to stop the motor rotation.

3.5 Ramps adjustment

The basic frequency (speed) profile is defined by parameters con-
tained in the "F" Group as shown to the right. The set running fre-
quency is in Hz, but acceleration and deceleration are specified in
the time duration of the ramp (from zero to maximum frequency,
or from maximum frequency to zero).
Acceleration 1 and Deceleration 1 are the standard default accel
and decel values for the main profile. Accel and decel values for an
alternative profile are specified by using parameters A092 through
A093.
Parameter
A004
A204
b082
F001
F002
F202
14
Parameter name
A002
RUN command selection
2nd RUN command selection
A202
Parameter name
b091
Stop selection
F002
Acceleration time 1
F202
2nd acceleration time 1
F003
Deceleration time 1
F203
2nd deceleration time 1
Parameter name
A003
Base frequency
A203
2nd base frequency
A082
AVR voltage selection
Parameter name
b012
Electronic thermal level
b212
2nd electronic thermal level
H003
Motor capacity selection
H203
2nd motor capacity selection
H004
Motor pole number selection
H204
2nd motor pole number selection
Parameter name
Maximum frequency
2nd maximum frequency
Starting frequency
Output frequency setting/monitor
Acceleration time 1
2nd acceleration time 1
Details
01: Terminal
02: Digital operator
03: ModBus communication
Details
00: Deceleration to stop
01: Free-run stop
0.01 to 3000. s
0.01 to 3000. s
Details
30. to Max. frequency [A004]
30. to Max. frequency [A204]
200-V class: 200/215/220/230/240 V
400-V class: 380/400/415/440/460/480 V
Details
0.2 x Rated current to 1.0 x Rated current
200-V class: 0.2/0.4/0.75/1.5/2.2/3.7/5.5/7.5 kW
400-V class: 0.4/0.75/1.5/2.2/3.7/5.5/7.5 kW
2/4/6/8 poles
Output frequency
Max. frequency
A004/A204
Actual
acceleration
time
F002/F202
Description
30. to 400. Hz
0.5 to 9.9 Hz
Starting frequency to 1st or 2nd max. frequency
0.01 to 3000. s
Output frequency set value
Actual
deceleration
time
F003/F203
JX Quick Start Guide