Chapter 2 Specifications; Performance Specifications - Mitsubishi Electric CC-Link IE Basic Reference Manual

Field network
Hide thumbs Also See for CC-Link IE:
Table of Contents

Advertisement

2
SPECIFICATIONS
This chapter describes the specifications of CC-Link IE Field Network Basic.
2.1

Performance Specifications

The following table lists the performance specifications of CC-Link IE Field Network Basic.
Item
Number of connectable modules per
network
Number of stations occupied by a slave station
Maximum number of link points per
network
Maximum number
Master station
of link points per
station
Slave station
UDP port number used in the cyclic transmission
UDP port number used in the automatic detection of connected
device
Transmission
Data transmission speed
specifications
Number of cascade
connections
Network topology
Connection cable
Maximum station-to-station distance
Overall cable distance
*1 It is the maximum number of connectable modules for a slave station controlled by the master station. It varies depending on the number
of stations occupied by a slave station. Ensure that the total number of occupied stations does not exceed the maximum number of
connectable modules.
*2 When using the programmable controller CPU (except for the R00CPU, R01CPU, and R02CPU) with the firmware version "28" or
earlier, refer to the following.
Page 9 Performance specifications vary depending on the version of the CPU module
*3 When using the CPU module with serial number earlier than "19042" (first five digits), refer to the following.
Page 9 Performance specifications vary depending on the version of the CPU module
2 SPECIFICATIONS
8
2.1 Performance Specifications
Specifications
MELSEC iQ-R
Master station
1
*1
64 (16  4 groups)
Slave station
1 to 4
*2
RX
4096
*2
RY
4096
*2
RWr
2048
*2
RWw
2048
*2
RX
4096
*2
RY
4096
*2
RWr
2048
*2
RWw
2048
RX
64 (1 station occupied)
128 (2 station occupied)
192 (3 station occupied)
256 (4 station occupied)
RY
64 (1 station occupied)
128 (2 station occupied)
192 (3 station occupied)
256 (4 station occupied)
RWr
32 (1 station occupied)
64 (2 station occupied)
96 (3 station occupied)
128 (4 station occupied)
RWw
32 (1 station occupied)
64 (2 station occupied)
96 (3 station occupied)
128 (4 station occupied)
61450
Master station: An unused port number is assigned automatically.
Slave station: 61451
100Mbps
100BASE-TX
For the number of the connectable stages when using a switching hub, check with the
manufacturer of the switching hub used.
Star topology
Ethernet cable compliant with the 100BASE-TX standard ( Page 18 Ethernet cable)
100m (ANSI/TIA/EIA-568-B (Category 5e) compliant)
Depends on the system configuration
MELSEC iQ-F
MELSEC-Q
*2
64 (16  4 groups)
6
*3
384
4096
*3
384
4096
*3
192
2048
*3
192
2048
*3
384
4096
*3
384
4096
*3
192
2048
*3
192
2048
MELSEC-L
*3
*3
16
*3
1024
*3
1024
*3
512
*3
512
*3
1024
*3
1024
*3
512
*3
512