If an error occurs while the automatic detection of connected device is being executed, the window shown below appears.
Each of the error codes listed below fills the last four digits of <0x2c09****>.
Error code
Error details and cause
480CH
The specified command cannot be executed because the
automatic detection of connected device is being executed.
480DH
• The specified command cannot be executed because the
communication setting reflection of slave station is being
executed.
• Communication timeout has occurred.
480EH
• The specified command cannot be executed because the
parameters processing of slave station is being executed.
• Communication timeout has occurred.
CF53H and
System error
CF56H
C059H
The function which is not supported by the target device
was executed.
C05CH
• The setting value of the communication setting is out of
range.
• Items of communication setting which cannot be set on
the target device are set.
• The required setting items have not been set to the target
device.
C061H
System error
CEE0H
The detection or another online function was executed by
another peripheral.
CEE1H and
System error
CEE2H
CF10H
System error
CF20H
• The setting value of the communication setting is out of
range.
• Items of communication setting which cannot be set on
the target device are set.
• The required setting items have not been set to the target
device.
CF30H
The parameter which is not supported by the target device
was specified.
Action
After the automatic detection of connected devices is completed, execute the
command again.
• After the communication setting reflection of slave station is completed,
execute the command again.
• Check and correct the communication time check setting value using the
engineering tool.
• Execute the command again after a while.
• Check and correct the communication time check setting value using the
engineering tool.
• Check the precautions for the function executed.
• Check the operating status and connection status of the target device.
• Check the connection of an Ethernet cable and a hub.
• Check the line status of Ethernet.
• Reset the CPU module and target device, and execute the function again.
If the above actions do not solve the problem, contact the manufacturer of
the target device.
Check whether the function executed is supported by the target device.
Correct the setting details, and retry the operation.
• Check the precautions for the function executed.
• Check the operating status and connection status of the target device.
• Check the connection of an Ethernet cable and a hub.
• Check the line status of Ethernet.
• Reset the CPU module and target device, and execute the function again.
If the above actions do not solve the problem, contact the manufacturer of
the target device.
Execute the other function after the automatic detection of connected
devices is completed.
• Check the precautions for the function executed.
• Check the operating status and connection status of the target device.
• Check the connection of an Ethernet cable and a hub.
• Check the line status of Ethernet.
• Reset the CPU module and target device, and execute the function again.
If the above actions do not solve the problem, contact the manufacturer of
the target device.
Correct the setting details, and retry the operation.
Check the version of the target device.
8.1 Settings for the Master Station in MELSEC iQ-R/MELSEC iQ-F
8 PARAMETER SETTINGS
8
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents