Modules and devices can be used as a slave station

For modules and devices which can be used as a slave station of CC-Link IE Field Network Basic, refer to the manual for
each module and device.
Use the CPU modules listed in the previous page (the CPU modules can be used as the master station) only
as the master station. ( Page 17 CPU modules can be used as the master station)

Wiring products

This section describes the wiring products used in CC-Link IE Field Network Basic.
Ethernet cable
Use an Ethernet cable which conforms to the following standards.
Ethernet cable
Category 5 or higher, (STP) straight cable
Category 5 or 5e, (STP) crossover cable
Hub
Use hubs which satisfy all the following conditions. If hubs not satisfying the conditions are used, operation is not guaranteed.
• IEEE802.3 (100BASE-TX) compliant
• The auto MDI/MDI-X function equipped
• The auto-negotiation function equipped
• Switching hub (layer 2 switch)
*1 A repeater hub cannot be used.
For switching hubs that can be used for CC-Link IE Field Network Basic, refer to the following.
Applicable products (switching hubs) for CC-Link IE Field Network Basic module (FA-A-0234)
5 SYSTEM CONFIGURATION
18
5.2 Product List
*1
Connector
Standard
RJ45 connector
• IEEE802.3 (100BASE-TX)
• ANSI/TIA/EIA-568-B (Category 5)