XNX Universal Transmitter
Modbus Holding
Datatype
Register Address
40007
uint8
40008
int16
40009 to 40010
float32
Appendix B - Modbus Protocol
Variable Name
This has the following meanings:
0
reserved
1
normal monitoring
2
in warm-up
3
long-term inhibit
4
alarm simulation
5
fault simulation
6
Loop current stimulated
7
in warning MFlt
8
in Instrument Flt
9
in beam block
10
in bump test
iMonitoringState
11
short-term inhibit
12
performing zero calibration
13
performing span calibration
14
in pre-zero calibration
15
in pre-span calibration
16
in post-zero calibration, successful
17
in post-span calibration, successful
18
in post-zero calibration, failed
19
in post-span calibration, failed
20
in align Excel mode
21-
for future expansion
255
This Heartbeat is provided to facilitate detection of communications problems in programming environments where the transport-
layer communication error information is unavailable. This increments approximately every 5 seconds.
iHeartBeat
It is the responsibility of the system integrator to notify plant personnel if a Modbus master fails to communicate with the XNX. This
register can facilitate this notification.
fSensorLifeDays
This indicates the time remaining before the ECC sensor must be calibrated or replaced.