Daikin FVXG25K2V1B Service Manual page 89

Pair, floor standing type k-series, heat pump, indoor/outdoor units
Hide thumbs Also See for FVXG25K2V1B:
Table of Contents

Advertisement

SiBE061121
Troubleshooting
Note:
Check the following connector.
Floor Standing Type
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the combination of the
indoor and outdoor unit.
OK?
YES
Check the connection of
connectors (See Note.).
OK?
NO
Correct the connection.
Error repeats?
NO
Model Type
NO
∗ To secure the connection,
once disconnect the connector
and then reconnect it.
YES
Check the power supply
voltage.
Voltage as rated?
YES
Start operation.
Error repeats?
NO
YES
Check the power supply
voltage.
Voltage as rated?
YES
Start operation.
Error repeats?
NO
Connector
Terminal board ~ Main PCB
Troubleshooting
Match the compatible
models.
NO
Correct the power
supply.
YES
Replace the indoor unit
PCB (1).
Completed.
NO
Correct the power
supply.
YES
Replace the indoor unit
PCB (1).
Completed.
Completed.
(R15270)