Outdoor Unit - RXG25/35K2V1B
Step
4
Disconnect the relay
connector for the
compressor.
Disconnect the
5
connector for the
outdoor electronic
expansion valve coil
[S20].
6
Cut the clamp.
Pull out the outdoor
7
heat exchanger
thermistor.
177
Procedure
(R11845)
[S20]
(R11847)
(R11850)
Be careful not to lose the clip
for the thermistor.
Outdoor heat
exchanger thermistor
(R11851)
SiBE061121
Points
Clip
Removal Procedure