Daikin FVXG25K2V1B Service Manual page 228

Pair, floor standing type k-series, heat pump, indoor/outdoor units
Hide thumbs Also See for FVXG25K2V1B:
Table of Contents

Advertisement

Outdoor Unit - RXG50K2V1B
Step
3
Release the clamp with
pliers to detach the
compressor lead wires.
4
Remove the putty.
Before working, make
sure that the refrigerant
gas is empty in the circuit.
Be sure to apply nitrogen
replacement when
heating up the brazed
part.
Heat up the brazed
5
parts indicated by the
arrows.
217
Procedure
SiBE061121
Points
Warning
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the
gas brazing machine.
Warning
If the refrigerant gas leaks
during work, ventilate the
room. (If the refrigerant gas is
exposed to flames, toxic gas
may be generated.)
Warning
Since it may happen that the
refrigerant oil in the
compressor catches fire,
prepare wet cloth so as to
extinguish fire immediately.
Caution
From the viewpoint of global
environment protection, do
not discharge the refrigerant
gas in the atmosphere. Make
sure to collect all the
refrigerant gas.
Removal Procedure