Daikin FVXG25K2V1B Service Manual page 101

Pair, floor standing type k-series, heat pump, indoor/outdoor units
Hide thumbs Also See for FVXG25K2V1B:
Table of Contents

Advertisement

SiBE061121
4.9.2 50 Class
E1
Remote
Controller
Display
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Service Diagnosis
Detection within the program of the microcomputer
The program of the microcomputer is in abnormal running order.
Defective outdoor unit PCB
Noise
Momentary fall of voltage
Momentary power failure
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn on the power again.
Error again?
NO
Check to see if the unit is
grounded.
Grounded?
YES
YES
NO
Troubleshooting
Replace the outdoor unit
PCB.
Ground the system.
The cause can be external
factors other than
malfunction.
Investigate the cause of
noise.
(R7183)
90