Daikin FVXG25K2V1B Service Manual page 181

Pair, floor standing type k-series, heat pump, indoor/outdoor units
Hide thumbs Also See for FVXG25K2V1B:
Table of Contents

Advertisement

SiBE061121
Step
3. Remove the fan motor.
Remove the nut of the
1
outdoor fan.
Remove the outdoor
2
fan.
3
Release the outdoor
temperature thermistor.
Removal Procedure
Procedure
Outdoor fan
D-cut
Outdoor temperature
thermistor
Outdoor Unit - RXG25/35K2V1B
Nut size: M6
(R14205)
When reassembling, align
mark of the outdoor fan
with D-cut section of the
motor shaft.
(R11828)
(R11829)
Points
10 mm
(R12236)
170