Daikin FVXG25K2V1B Service Manual page 229

Pair, floor standing type k-series, heat pump, indoor/outdoor units
Hide thumbs Also See for FVXG25K2V1B:
Table of Contents

Advertisement

SiBE061121
Step
6
Remove the 2 nuts of
the compressor.
7
Heat up the brazed part
of the discharge side
and disconnect.
8
Heat up the brazed part
of the suction side and
disconnect.
Lift the compressor up
9
and remove it.
Removal Procedure
Procedure
Outdoor Unit - RXG50K2V1B
Cautions for restoration
1. Restore the piping by non-
oxidation brazing.
2. It is required to prevent the
carbonization of the oil inside
the four way valve and the
deterioration of the gaskets
affected by heat. (Keep
below 120°C.) For the sake
of this, wrap the four way
valve with wet cloth and
provide water so that the
cloth does not dry.
In case of difficulty with gas
brazing machine
1. Disconnect the brazed part
where is easy to disconnect
and restore.
(R10257)
2. Cut pipes on the main unit
with a tube cutter in order to
make it easy to disconnect.
Note:
Do not use a metal saw for
cutting pipes by all means
because the sawdust comes
into the circuit.
When withdrawing the pipes,
be careful not to pinch them
firmly with pliers. The pipes
may get deformed.
Provide a protective sheet or
a steel plate so that the
brazing flame cannot
influence peripheries.
Be careful so as not to burn
the compressor terminals,
the name plate, the heat
exchanger fins.
Points
218