INSTALLATION OF NON-COMBUSTIBLE WALL AND HEARTH BOARD:

Install the non-combustible wall board and hearth protector provided with the
unit. The side boards are interchangeable and are secured with facing screws
(¾" screws provided), three (3) to each side of the unit and three (3) to each
side frame member. The top board is secured with three (3) facing screws along
the top frame (header), three (3) along the top nailing flange of the unit and two
(2) on each vertical frame member. Also secure the top wall board to the heat
shield behind it with two (2) screws and each facing support upright with two (2)
screws. See the section on hearth installation for installing the hearth protector,
required with the installation of this unit. All the screws required to attach the
wall board sides and top to the unit have corresponding holes already located
on the units nailing flanges, facing supports and heat shield.

INSTALLATION OF VENTING AND TERMINATIONS:

Read all instructions carefully before starting the installation. Failure to follow
these instructions may create a fire or other safety hazard, and will void the
warranty.
INSTALLATION PRECAUTIONS:
• D o not install any damaged venting or vent components.
• Do not modify any vent or termination component.
• D o not install any vent component that is not an approved vent component
for this appliance.
• D o not use any instructions other that those included in this manual or those
included by the vent component manufacturer with the venting. When there
are discrepancies between the two, this manual will be considered the final authority.
Consult your local building codes before beginning the installation.
Figure 32: Typical Minimum Vent Configurations
- Horizontally Terminated.
QUALIFIED INSTALLERS ONLY
installation
Figure 31: Installation of Wall & Hearth Board.
Vertical Termination
Storm Collar
Roof Flashing
Fire Stop
Vent Sections
45° Elbow
Figure 33: Typical Vent Configurations
- Vertically Terminated.
HZ965/L965 Gas Fireplace |
|
21
Non-Combustible
Hearth Protection