Venting Arrangements - Horizontal Termination (Flex) - Regency Liberty L965E Owners And Installation Manual

Gas fireplace
Hide thumbs Also See for Liberty L965E:
Table of Contents

Advertisement

Table 5: Minimum 'H' for Figure 44.
Roof Pitch
Flat to 7/12
Over 7/12 to 8/12
Over 8/12 to 9/12
Over 9/12 to 10/12
Over 10/12 to 11/12
Over 11/12 to 12/12
Over 12/12 to 14/12
Over 14/12 to 16/12
Over 16/12 to 18/12
Over 18/12 to 20/12
Over 20/12 to 21/12

VENTING ARRANGEMENTS - HORIZONTAL TERMINATION (FLEX):

Regency
Direct Vent System
®
These venting systems, in combination with the HZ965/L965, have been tested and listed as a direct vent system by Warnock Hersey. The
location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination
Locations" section.
FPI Direct Vent (Flex) System Termination Kits include all the
parts needed to install the HZ965/L965, using a flexible vent.
FPI Kit #
Length
Contains:
#946-615
4 Feet
1) 8" flexible liner (Kit length)
2) 5" flexible liner (Kit length)
3) spring spacers
4) thimble
#946-618
6 Feet
5) AstroCap termination cap
6) screws
7) tube of Mill Pac
#946-616
10 Feet
8) plated screws
9) S.S. screws #8 x 1-1/2" drill point
10) vinyl siding standoff
Minimum Height (H)
Feet
Meters
1
0.3
1.5
0.46
2
0.61
2.5
0.76
3.25
0.99
4
1.22
5
1.52
6
1.83
7
2.13
7.5
2.29
8
2.44
installation
Dimension 'H' obtained
from table to the left.
Figure 44: Height of Vertical Termination;
Reference Table 5.
Rigid pipe adaptor
(Part # 946-601)
(standard with unit)
HZ965/L965 Gas Fireplace |
|
25
H
25