Steps - Viessmann VITODENS 200 Start-Up And Service Instructions

Wb2 series wall-mounted, gas-fired condensing boiler
Hide thumbs Also See for VITODENS 200:
Table of Contents

Advertisement

Steps

I
nitial start-up
1. Fill heating system with water
1. Open system isolation valves (if
installed).
2. Check inlet pressure of the
diaphragm expansion tank.
3. To remove debris and/or sludge
ensure that the system piping is
flushed out. Failure to do so could
cause settlement in the boiler
causing overheating and damage
not covered by warranty.
4. Optional:
Fill the heating system with water
at the boiler filling and drain tap
and drain air completely from the
system at ball valve barb fitting
Max. boiler
operating pressure
Min. boiler
operating pressure
Pressure relief valve ......30 psig
Air vent
Initial Start-up and Service
Please note:
Before filling the heating system with
water, check that all necessary flow
check valves are installed.
If the nitrogen pressure of the
precharged expansion tank is less
than the static pressure of the
system, inflate membrane pressure to
slightly exceed pressure of system.
The static pressure required at the
tank is based upon the static height
of the system. The system fill
pressure value must be equal to the
expansion tank pressure value at
approx. 60 ºF/15.6 ºC.
System fill pressure must be
approximately 3 psig higher than the
static head when the system is cold.
Water treatment should be
considered in areas where it is known
that boiler feed water contains a high
mineral content and hardness.
.
In areas where freezing might occur,
an antifreeze may be added to the
system water to protect the system.
......45 psig
Please adhere to the specifications
given by the antifreeze manufacturer.
......12 psig
Do not use automotive silicate-based
antifreeze. Please observe that an
antifreeze/water mixture may require
a backflow preventer within the
automatic water feed and influence
components such as diaphragm
expansion tanks, radiation, etc. A
40% antifreeze content will provide
freeze-up protection to -10°F/-23°C.
Do not use antifreeze other than
specifically made for hot water
heating systems. System also may
contain components which might be
negatively affected by antifreeze.
Check total system frequently when
filled with antifreeze.
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wb2-44/60

Table of Contents