Control Unit for Weather-Responsive Operation
Overview of coding addresses (continued)
Coding (factory
Function mode
default setting)
Address: Value
016:000
Do not change
017:001
Do not change
018:000
DHW
tank
019:000
Program-
ming
unit or
remote
control
020:000
Heating
circuits
027:000
External switching of heating program
028:000
Boiler
029:001
Do not change
033:000
Do not change
034:000
Do not change
036:000
Do not change
038:020
Minimum supply temperature in heating mode 020 to 127
*1
Change only feasible if programming unit is mounted on a wall-mount base.
*2
Address set automatically, must be reset manually.
Circulating pump with time
delay function
Weather-responsive operation
(WS function) for all con-
nected heating circuits
Without WS or RS remote
control unit
During DHW production, the
boiler water temp. is max. 36
ºF / 20 ºC higher than the
desired tank water temp.
with programming unit
(continued)
Coding
Possible change
change
Address: Value
018:001
Circulating pump without time delay function
*1
019:001
H On systems with one heating circuit
without mixing valve or one heating
circuit with mixing valve:
Operation with room temperature
dependent control (RS function)
H On systems with one heating circuit
without mixing valve and one heating circuit
with mixing valve:
Weather-responsive operation (WS function)
for heating circuit with mixing valve and op-
eration with room temperature dependent
control (RS function) for heating circuit with
mixing valve
*1
019:002
H On systems with one heating circuit
without mixing valve or one heating
circuit with mixing valve:
Weather-responsive operation (WS function)
in normal heating mode and operation with
room temperature dependent control (RS
function) in reduced operation
H On systems with one heating circuit
without mixing valve and one heating circuit
with mixing valve:
Weather-responsive operation (WS function)
for heating circuit without mixing valve and
on weather-responsive basis in normal heat-
ing mode and operation with room tempera-
ture dependent control in reduced operation
(WS/RS function) for heating circuit with
mixing valve
020:001
With WS or RS remote control unit
027:001
External call for heat
028:001
During domestic hot water production, the
boiler water temperature is limited to
172 ºF/78 ºC by the limit thermostat
Min. possible supply temperature
68 to 261 ºF / 20 to 127 ºC
Additional Information