Viessmann VITODENS 200 Start-Up And Service Instructions page 56

Wb2 series wall-mounted, gas-fired condensing boiler
Hide thumbs Also See for VITODENS 200:
Table of Contents

Advertisement

Additional Information
Control Unit for Weather-Responsive Operation
Overview of coding addresses (continued)
Coding (factory
Function mode
default setting)
Address: Value
0A9:098
Circulating
pump
0B2:___
Fault memory (see page 28)
0B3:___
Fault memory (see page 28)
0B4:___
Do not change
0B8:000
Space heating only - no DHW
0C1:011
Freeze-up protection threshold
+34 / +37 ºF or +1 / +3 ºC
0C2:008
Do not change
0C5:000
Boiler
Possible coding changes for coding address 0C5 "external heat demand"
Coding
Heating circuit
pump
pump
0C5:000
ON
0C5:001
OFF
0C5:002
×
0C5:003
OFF
0C5:004
ON
0C5:005
×
0C5:006
OFF
0C5:007
ON
0C5:008
×
0C5:009
OFF
0C5:010
ON
0C5:011
×
× = in normal control mode
*1
One increment corresponds to approx. 20 rpm.
*2
This is set automatically when a tank temperature sensor is connected; can be reset to "001" manually if required.
*3
Once this function has ended, the program changes automatically to the "Space heating and DHW heating" mode.
56
Max. rotational speed of cir-
culating pump for DHW pro-
duction
See table below for effect of
external heat demand signal
(also see page 59)
Heating circuit with mixing valve
(extension kit)
Heating circuit pump
OFF
OFF
OFF
×
×
×
OFF
OFF
OFF
×
×
×
with programming unit
(continued)
Coding
Possible changes
change
Address: Value
0A9:001
Lowest value for rotational speed of
to
circulating pump for DHW production
*1
0A9:100
Highest value for rotational speed of
circulating pump for DHW production
0B8:001
With DHW heating
0B8:002
Optimum DHW heating (with anti legionnaire
function) (see page 48).
0B8:005
Combi boiler only
0B8:006
Not assigned. Must be changed to one of the
other coding addresses.
0C1:000
+50 / +18 ºF or +10 / –8 ºC
0C1:015
+41 / +45 ºF or +5 / +7 ºC
*3
0C5:001
See table below for effect of external
to
heat demand signal
0C5:011
*3
Circulating pump
for tank heating
for tank heating
Mixing valve
CLOSED
OFF
CLOSED
OFF
CLOSED
OFF
×
OFF
×
OFF
×
OFF
CLOSED
×
CLOSED
×
CLOSED
×
×
×
×
×
×
×
Boiler water
temperature
temperature
Maintained at
desired value
d i d
l
according to
according to
coding address
g
"0A2"
"0A2"