Overview Of Coding Addresses - Viessmann VITODENS 200 Start-Up And Service Instructions

Wb2 series wall-mounted, gas-fired condensing boiler
Hide thumbs Also See for VITODENS 200:
Table of Contents

Advertisement

Additional Information
Control Unit for Weather-Responsive Operation

Overview of coding addresses

Coding (factory
Function mode
default setting)
Address: Value
000:000
One heating circuit without mixing valve,
system without domestic hot water heat-
ing
001:000
Do not change
003:001
DHW
tank
004:000
Do not change
005:001
Heating
circuit
pump
006:001
Heating
circuit
pump
007:000
DHW
tank
008:000
Do not change
009:000
Program-
ming unit
010:000
Do not change
011:000
External call for heat or external
switching of heating program blocked
012:000
Do not change
013:000
Heating
circuit
pump
*3
014:000
Heating
circuit
015:001
Do not change
*1
Coding for systems with domestic hot water heating is automatically recognized.
*2
These codings also apply on systems with one heating circuit without mixing valve and one heating circuit with mixing valve.
*3
Only on heating system types "000:002" and "000:003" (heating systems with one heating circuit with mixing valve).
52
Coding addresses not discussed in this section must not be
changed.
See page 50 for information of how to access coding addresses.
With priority switching over
heating circuit pump(s)
With heating circuit pump
logic function
Heating circuit pump speed in
reduced range as per
coding address "044:..."
Setting range of domestic hot
water temperature
50 to 140 ºF/10 to 60 ºC
Display of boiler water
temperature
Heating circuit pump without
variable speed operation (e.g.
as temporary measure for
servicing)
Party button "g" effective
for heating circuit B
with programming unit
(continued)
Coding
Possible change
change
Address: Value
*1
000:001
One heating circuit without mixing valve,
system with domestic hot water heating
*2
000:002
One heating circuit with mixing valve,
system without domestic hot water heating
*1, 2
000:003
One heating circuit with mixing valve,
system with domestic hot water heating
003:000
Without priority switching over heating circuit
pump(s)
005:000
Without heating circuit pump logic function
006:000
Heating circuit pump speed in reduced range
as per coding address "046:..."
007:001
Setting range of domestic hot water tempera-
ture 50 to 158 ºF/10 to 70 ºC
IMPORTANT
Note max. tank water temperature.
IMPORTANT
Do not adjust domestic hot water
temperature more than 140 ºF/
60 ºC.
009:001
Display of outdoor temperature
011:001
External call for heat or external switching of
heating program active at X4.1 - X4.2
013:001
With variable speed heating circuit pump (au-
tomatic
recognition)
*3
014:001
Party button "g" effective for heating circuit
A and heating circuit B