Appendix A
Constant
Indi-
no.
cators
n21
n24
n25
n26
n31
n33
n36
n37
n39
n40
n61
n64
Note 1. The upper limit of setting range and the factory settings for the 400-VAC-class
Inverters are double the above values.
Note 2. The setting range of the 400-VAC-class Inverter is "1 to 5." The factory setting of
the 3G3EV-A4015M-CUE is "3."
Note 3. Values in shaded sections or values in brackets represent factory settings.
Description
Deceleration
0.0 to 999 (seconds)
time
Maximum
50.0 to 400 (Hz)
frequency
Maximum
1 to 255 (V) (see note 1)
voltage
Maximum
1.6 to 400 (Hz)
voltage
frequency (basic
frequency)
Electronic
0.0 to 120% of rated Inverter amperage
thermal
Specify the rated motor amperage.
reference
current
Stall prevention
0: Stall prevention
during
1: No stall prevention
deceleration
Operation after
0: Discontinues operation.
recovery from
1: Continues operation only if the power
power
interruption
2: Continues operation unconditionally.
Carrier
1: 2.5 (kHz) (see note 2)
frequency
2: 5 (kHz)
3: 7.5 (kHz)
4: 10 (kHz)
Frequency
0.10 to 2.00 (times)
reference gain
Frequency
–99 to 99 (%)
reference bias
Stop Key
0, 1
selection
Operator's
0, 1
frequency
setting method
Setting range
interruption is within 0.5 second.
Chapter 7
Setting
[10.0]
[60.0]
[200]
[60.0]
[1.00]
[0]
[0]
[0]
7-11