Preparing for Operation
Note 3. The setting range for the 400-VAC models is "1 to 5."
Note 4. The factory setting for the 3G3EV-A4015-CUE is "3."
Note 5. Displaying the constant no. corresponding to an indicator in the "Dedicated
indicator" column lights the indicator.
Note 6. Constant no. 02 (n02) and subsequent constants can be set only when
constant no. 01 (n01) is set to 1.
Constants in the shaded areas in the above table may not be usable depending on the
PROM number (software version).
Con-
stant
199 or lower
no.
n03
No
n39
Setting range: 0.10 to 2.00 Setting range: 0.10 to 2.00 Setting range: 0.10 to 2.55
n61
No
n64
No
Note "Yes" indicates that the constant can be set.
"No" indicates that the constant cannot be set.
H Details of Each Constant
n01
Constant Write-Inhibit Selection/Constant Initialization
Setting range
One of the following four values can be selected:
Value
0
Only n01 can be set.
1
Constants n01 to n68 can be displayed and set.
8
All constants are returned to factory settings.
9
The Inverter is initialized in 3-wire sequence mode.
Note 1. If other constants are to be set, always set "1" in n01.
Note 2. Setting "9" (3-wire sequence mode) in n01 allows the user to start and stop the
Inverter with automatic recovery type push-button switches.
PROM no. (software version)
Yes
Yes
No
0, 1, 8, 9
200
Yes
Yes
Yes
Factory setting 1
Description
Chapter 4
220 or higher
4-11