Preparing for Operation
Note 2. The factory setting for the 3G3EV-A4015-CUE is "3."
Note 3. With the 400-VAC class, the continuous output current cannot be used to 100%
of the rated value if the constant is set to "5" for Inverters of 0.75 kW or less or if it
is set to "4" or "5" for an Inverter of 1.5 kW.
Set the constant so that the continuous output current does not exceed the val-
ues shown in the following tables.
400-VAC Inverters of 0.75 kW or Less
Carrier frequency set value
1 to 4
5
400-VAC Inverter of 1.5 kW
Carrier frequency set value
1 to 3
4
5
Max. continuous output current
Up to 100% of the rated output
Up to 90% of the rated output
Max. continuous output current
Up to 100% of the rated output
Up to 85% of the rated output
Up to 75% of the rated output
Chapter 4
4-21