Omron SYSDRIVE 3G3EV User Manual page 28

Compact low-noise inverter
Hide thumbs Also See for SYSDRIVE 3G3EV:
Table of Contents

Advertisement

Design
Induction Noise: Electromagnetic induction generates noise on the signal line, causing
the controller to malfunction.
Radio Noise:
Electromagnetic waves from the Inverter and cables cause the
broadcasting radio receiver to make noise.
D How to Prevent Induction Noise
As described above, a noise filter can be used to prevent induction noise from being
generated on the output side. Alternatively, cables can be routed through a grounded
metal pipe to prevent induction noise. Keeping the metal pipe at least 30 cm away from
the signal line considerably reduces induction noise.
Power supply
D How to Prevent Radio Noise
Radio noise is generated from the Inverter as well as the input and output lines. To re-
duce radio noise, install noise filters on both input and output sides, and also install the
Inverter in a totally enclosed steel box.
The cable between the Inverter and the motor should be as short as possible.
Power supply
MCCB
3G3EV
Signal line
Steel box
3G3EV
Noise
filter
Metal pipe
30 cm min.
Controller
Metal pipe
Noise
filter
Chapter 3
3-15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysdrive 3g3ev series

Table of Contents