Fujitsu ASG30LMTA Service Instruction page 58

Wall mounted type inverter
Table of Contents

Advertisement

Trouble shooting 22
OUTDOOR UNIT Error Method:
Heat Ex. Liquid Outlet Thermistor Error
Detective Actuators:
Outdoor unit Main PCB
Heat exchanger temperature thermistor
Forecast of Cause :
1. Connector connection failure
Check Point 1 : Check connection of connector
Check if connector is removed.
Check if connector is erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
Temperature
(°C )
Resistance value (k )
Temperature
(°C )
Resistance value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
Thermistor
(Compressor temp.)
BROWN
3
3
2
2
CN64
BROWN
1
1
Thermistor
(Outdoor temp.)
BLUE
3
3
CN62
2
2
BLUE
1
1
Thermistor
(Heat exchanger)
BLACK
3
3
CN65
2
2
BLACK
1
1
Thermistor
(Discharge pipe)
BROWN
3
3
CN63
2
2
BROWN
1
1
If the voltage does not appear, replace Main PCB.
AMP Air Conditioning
Indicate or Display:
Indoor Unit :
Operation lamp: 7 times Flash,
Timer lamp
Detective details:
When Heat exchanger temperature thermistor open or
short-circuit is detected at power ON or while running the compressor.
2. Thermistor failure
-30
-20
-10
5 -
92.3
49.2
27.5
20.9
20
3
0
4
0
5
0
6.1
4.0
2.6
1.8
02-25
Wired Remote Controller :
ERROR CODE : [E : 73]
: 3 times Flash
3. Main PCB failure
0
5
10
15
16.1
12.4
9.7
7.7
6
0
70
80
1.3
0.9
0.7
0.5