Trouble shooting 4
INDOOR UNIT Error Method:
External communication error
Detective Actuators:
External communication error
Forecast of Cause :
1. Connection failure
Check Point 1 : Check the connection
Check any loose or removed connection of between the controller PCB to the external I/OPCB
>>If there is an abnormal condition, correct it by refer to installation manual or
the technical manual.
Check the connection condition on the external I/O PCB and the controller PCB
(If there is loose connector, open cable or mis-wiring)
OK
OK
Check Point 2: Replace external I/O PCB
If Check Point 1 do not improve the symptom, change External I/O PCB.
OK
OK
Check Point 3: Replace Controller PCB
If Check Point 2 do not improve the symptom, change Controller PCB.
AMP Air Conditioning
Indicate or Display:
Indoor Unit :
Operation lamp: 1 times Flash,
Timer lamp
Detective details:
After receiving a signal from the external I/O PCB,
the same a signal has not been received for 15sec
2.External I/O PCB failure
: 8 times Flash
3.Controller PCB failure
02-07
www.ampair.co.uk | sales@ampair.co.uk
Wired Remote Controller :
ERROR CODE : [E : 18]