Fujitsu ASG30LMTA Service Instruction page 43

Wall mounted type inverter
Table of Contents

Advertisement

Trouble shooting 7
INDOOR UNIT Error Method:
Connection unit number error (Indoor
unit in Wired remote controller system)
Detective Actuators:
Wired remote controller ( 2-Wire )
Indoor unit Controller PCB circuit
Forecast of Cause : 1. Wrong wiring / Number of I.U, RC in RCgroup 2. Indoor unit controller PCB defective
Check Point 1 : Wire installation
Wrong number of connecting indoor unit
Check Point 2 : Check Indoor unit controller PCB
Check if controller PCB damage
Check if controller PCB and check the Error after setting remote controller address
AMP Air Conditioning
Indicate or Display:
Indoor Unit :
Operation lamp: 2 times Flash,
Timer lamp
: 9 times Flash
Detective details:
When the number of connecting indoor units are out of specified rule.
02-10
Wired Remote Controller :
ERROR CODE : [E : 29]
www.ampair.co.uk | sales@ampair.co.uk

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rsg30lmtaRsg36lmtaAog30lmtaRog30lmtaAsg36lmtaAog36lmta ... Show all

Table of Contents