Trouble shooting 12
INDOOR UNIT Error Method:
Indoor Heat Ex. Thermistor Error
Detective Actuators:
Indoor unit Controller PCB
Heat exchanger (MID) Thermistor
Forecast of Cause : 1. Connector failure connection 2. Thermistor failure 3. Controller PCB failuer
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature
(°C )
Resistance value (k )
Temperature
(°C )
Resistance value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
BLACK
1
1
BLACK
2
2
CN1
BLACK
3
3
BLACK
4
4
If the voltage does not appear, replace Controller PCB and execute the check operation again.
AMP Air Conditioning
Indicate or Display:
Indoor Unit :
Operation lamp: 4 times Flash,
Timer lamp
Detective details:
Heat exchanger (MID) thermistor is open or short is detected always.
-30
-25
-20
1131.9
804.5
579.6
20
25
30
62.9
49.7
39.6
Thermistor ( Pipe temp.)
Thermistor ( Room Temp.)
Wired Remote Controller :
ERROR CODE : [E : 42]
: 2 times Flash
-15
-10
-5
422.9
312.3
233.2
176.0
35
40
45
31.7
25.6
20.9
02-15
www.ampair.co.uk | sales@ampair.co.uk
0
5
10
134.2
103.3
80.3
50
55
60
11.6
10.4
17.1
14.1
15
63