Trouble shooting 11
INDOOR UNIT Error Method:
Indoor Room Thermistor Error
Detective Actuators:
Indoor unit Controller PCB
Room temperature thermistor
Forecast of Cause : 1. Connector failure connection 2. Thermistor failure 3. Controller PCB failuer
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature
(°C )
Resistance value (k )
Temperature
(°C )
Resistance value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
BLACK
1
1
BLACK
2
2
CN1
BLACK
3
3
BLACK
4
4
If the voltage does not appear, replace Controller PCB and execute the check operation again.
AMP Air Conditioning
Indicate or Display:
Indoor Unit :
Operation lamp: 4 times Flash,
Timer lamp
Detective details:
Room temperature thermistor is open or short is detected always.
-10
-5
0
58.3
44.0
33.6
25.9
30
35
40
8.0
6.5
5.3
Thermistor( Pipe temp.)
Thermistor( Room Temp.)
Wired Remote Controller :
ERROR CODE : [E : 41]
: 1 times Flash
5
10
15
20
20.2
15.8
12.5
45
4.4
02-14
www.ampair.co.uk | sales@ampair.co.uk
25
10.0
DC