Users Manual

Set the Reference

The reference procedure for twisted pair cable sets the baseline
for insertion loss, ACR-F, and DC resistance measurements.
Set the reference at these times:
When you want to use the tester with a different remote. You
can set the reference for eight different remotes.
When you attach Class F/F
optional DSX-PLA011 TERA
Every 30 days. This ensures maximum accuracy of test results.
It is not necessary to set the reference when you change the link
interface adapters.
To set the reference
1
Turn on the tester and the remote a minimum of 1 minute
before you set the reference.
Set the reference only after the testers are at an
ambient temperature between 50 °F and 104 °F
(10 °C and 40 °C).
2
Connect the main and remote testers together as shown in
Figure 12.
3
If you attached Class F/F
you select a Class F or F
supplied with the adapters.
4
On the home screen, tap TOOLS, then tap Set Reference.
5
On the SET REFERENCE screen tap TEST.