Preparing the Site

This chapter includes the following sections:

Humidity Requirements

High humidity can cause moisture to seep into the switch. Moisture can cause corrosion of internal components
and degradation of properties such as electrical resistance, thermal conductivity, physical strength, and size.
The switch is rated to operate at 8 to 80 percent relative humidity, with a humidity gradation of 10 percent
per hour.
The switch can withstand from 5 to 90 percent relative humidity. Buildings in which the climate is controlled
by air-conditioning in the warmer months and by heat during the colder months usually maintain an acceptable
level of humidity for the switch equipment. However, if the switch is located in an unusually humid location,
you should use a dehumidifier to maintain the humidity within an acceptable range.

Altitude Requirements

If you operate a switch at a high altitude (low pressure), the efficiency of forced and convection cooling is
reduced and can result in electrical problems that are related to arcing and corona effects. This condition can
also cause sealed components with internal pressure, such as electrolytic capacitors, to fail or to perform at a
Humidity Requirements, page 3
Altitude Requirements, page 3
Dust and Particulate Requirements, page 4
Minimizing Electromagnetic and Radio Frequency Interference, page 4
Shock and Vibration Requirements, page 5
Grounding Requirements, page 5
Planning for Power Requirements, page 5
Rack and Cabinet Requirements, page 8
Clearance Requirements, page 10
2
C H A P T E R
Cisco Nexus 7702 Hardware Installation Guide
3