Indicators And Troubleshooting; Explanation Of Response Message Devices; Power Indicator; Run Indicator - Delta DVP-ES2 Operation Manual

Hide thumbs Also See for DVP-ES2:
Table of Contents

Advertisement

value of D6000 is judged as 101(hex), the ReqID is changed into 2 and D6250 is given a new
value 201(hex) and DVP-ES2-C sends out the request message again. By dong so, the
real-time reading can be realized. After reading succeeds, the data returning from the target
device are stored in D6000~D6005. The value of D6005: 100 ( hex) is the read value of P0-09.

Explanation of Response Message Devices:

PLC device
D6000
D6001
SDO
D6002
response
message
D6003
mapping
D6004
area
D6005
D6006
7.5

Indicators and Troubleshooting

There are 6 LED indicators on DVP-ES2-C. Power indicator shows whether the power is normal,
RUN and ERROR indicator display the state of running of internal program and COM3 displays the
communication state of CANopen.
7.5.1 Description of Indicators

POWER indicator

LED indicator
Light is off or
The supply power is
the green light
abnormal
flashes
The green
The supply power is
light keeps on
normal

RUN indicator

LED indicator
The green
PLC is running
light is on.
Light is off
PLC is in stop status
ERROR indicator
LED indicator
Light is off
PLC is normal
There are syntax
error existing in the
program written to
The red light
PLC or the PLC
flashes.
device or instruction
is out of the allowed
range.
The red light
PLC scan is
keeps on.
timed-out
COM3(CANopen)Indicator
LED indicator
The green
DVP-ES2-C is
light keeps on.
normal.
The green
light is in
DVP-ES2-C stops.
single flash.
Content
(Hex)
High byte(Hex)
0101
ResID = 01
0008
Reserved
4302
Type = 43
2009
Main index high byte = 20
0004
Reserved
0100
Datum 1= 01
0100
Datum 3= 00
Description
Check if the supply power is in the valid range
No resolution is required
Description
No resolution is required
Make PLC run through RUN/STOP switch or
WPLSoft
Description
No resolution is required
Judge the error cause according to the content
value of the special register D1004 in PLC; find
the program error position according to the
content value of D1137. For more details on the
error codes in D1004, please refer to "ES2 series
PLC operation manual (Programming)".
Reduce the time for executing PLC program or
use WDT instruction
Description
No resolution is required
The superior equipment is downloading the
network configuration and waiting to complete
downloading.
7 CANope n Func t i on a nd O pe r a t i on
Explanation
Low byte(Hex)
Status code = 01
Size = 08
Node ID = 02
Index low byte = 09
Subindex = 00
Datum 0= 00
Datum 2= 00
How to deal with
How to deal with
How to deal with
How to deal with
7 - 2 3