3.5.5 Pr. 1, 2 Upper-limit/lower-limit frequency

These parameters can be used to restrict motor speed.
These parameters are used to set upper and lower limits on output frequency.
Pr.
1
Upper-limit frequency
2
Lower-limit frequency
(1) Set upper-limit frequency
● Use Pr. 1 Upper-limit frequency to set the maximum
frequency. If the frequency of the frequency
command entered is higher than the setting, the
output frequency is clamped at the upper-limit
frequency.
(2) Set lower-limit frequency
● Use Pr. 2 Lower-limit frequency to set the minimum
frequency.
● If the set frequency is less than Pr. 2, the output
frequency is clamped at Pr. 2 (will not fall below Pr. 2 ).
Screen at power-ON
1
The monitor display appears.
Changing the operation mode
2
Press
to choose the PU operation mode. The [PU] indicator turns on.
Parameter setting mode
3
Press
to choose the parameter setting mode.
Selecting the parameter number
4
Turn
until
Reading settings
5
Press
to read the present setting. "
Changing the setting
6
Turn
to change the setting to "
Parameter settings
7
Press
to finalize the setting.
The parameter number and setting flashes.
* Configure parameter settings in accordance with your environment.
Name
Initial value
120Hz
0Hz
Operation example
(Pr. 1) is selected.
" (60.00Hz).
Setting range
0 to 120Hz
0 to 120Hz
Output frequency
(Hz)
Pr.1
Pr.18
Pr.2
0
(4mA)
Clamped at the
lower-limit frequency
" (120.0Hz (initial value)) appears.
3-12
Description
Upper limit of the output frequency
Lower limit of the output frequency
Clamped at the
upper-limit frequency
Frequency setting value
5, 10V
(20mA)