Mitsubishi FREQROL-E700 Manual page 30

Satellite training series
Table of Contents

Advertisement

Above inverter
Heat is blown up from inside the inverter by the small fan built in the unit.
Any equipment placed above the inverter should be heat resistant.
Arrangement of multiple inverters
When multiple inverters are placed in the same enclosure, generally arrange them horizontally as shown below in the
figure (a). When it is inevitable to arrange them vertically to minimize space, take such measures as to provide guides
since heat from the bottom inverters can increase the temperatures in the top inverters, causing inverter failures.
When mounting multiple inverters, fully take caution not to make the surrounding air temperature of the inverter
higher than the permissible value by providing ventilation and increasing the panel size.
Inverter
Inverter
Inverter
Inverter
Guide
Guide
Guide
Inverter
Inverter
Enclosure
Enclosure
(a) Arranged horizontally
(b) Arranged vertically
Arrangement of multiple inverters
Arrangement of ventilation fan and inverter
Heat generated in the inverter is blown up from the bottom of the unit as warm air by the cooling fan. When install-
ing a ventilation fan for that heat, determine the place of ventilation fan installation after fully considering an air flow.
(Air passes through areas of low resistance. Make an airway and airflow plates to expose the inverter to cool air.)
Inverter
Inverter
<Good example>
<Bad example>
Arrangement of the ventilation fan and inverter
2-12