Mitsubishi FREQROL-E700 Manual page 105

Satellite training series
Table of Contents

Advertisement

Sink logic
Main circuit terminal
Control circuit terminal
Single-phase power input
MCCB
MC
Single-phase
AC power
supply
MCCB
Three-phase
AC power
supply
Control input signals (No voltage input allowed)
Forward
Terminal functions vary
rotation start
with the input terminal
Reverse
assignment (Pr. 178 to
rotation start
Pr. 184)
High
speed
Middle
Multi-speed selection
speed
*2 When using terminals PC-
Low
SD as a 24VDC power
speed
supply, take care not to
Output
short across terminals
stop
PC-SD.
Reset
Contact input common
24VDC power supply
(Common for external power supply transistor)
Frequency setting signals (Analog)
*3 Terminal input specifications
Frequency
can be changed by analog
setting
input specifications
potentiometer
switchover (Pr. 73).
1/2W1kΩ
*4 It is recommended to use 2W1kΩ
when the frequency setting signal
is changed frequently.
Terminal 4 input
(Current input)
*5 Terminal input specifications can be changed by analog
input specifications switchover (Pr. 267). Set the
voltage/current input switch in the "V" position to select
voltage input (0 to 5V/0 to10V) and "I" (initial value) to
select current input (4 to 20mA).
To use terminal 4 (initial setting is current input), set "4"
in any of Pr.178 to Pr.184 (input terminal function selection)
to assign the function, and turn ON AU signal.
Connector for
plug-in option connection
*
1. DC reactor (FR-HEL)
When connecting a DC reactor, remove the
jumper across P1-P/+
Single-phase 100V power input model is not
compatible with DC reactor.
R/L1
Earth
S/L2
(Ground)
Jumper
P1
MC
*6
R/L1
S/L2
T/L3
Earth
(Ground)
Control circuit
STF
STR
RH
RM
RL
MRS
RES
SD
*2
PC
10(+5V)
3
2 0 to 5VDC
2
(0 to 10VDC)
*4
5(Analog common)
1
(+)
4 4 to 20mADC
(-)
0 to 5VDC
0 to 10VDC
I
V
Voltage/current
input switch
Option connector
FR-E700-NA
App.4-3
Brake unit
(Option)
*1
R
*8
PR N/-
*7
P/+
Inrush current
V
limit circuit
W
Main circuit
Standard control terminal block
C
B
Relay output
(Fault output)
A
RUN
Running
FU
Frequency detection
Open collector output common
SE
Sink/source common
24V
AM
5
*3
PU
connector
*5
USB
connector
*5
*6 Terminal P1 is not available for single-phase
100V power input model.
*7 A brake transistor is not built-in to the
FR-E720-008 and 015, FR-E720S-008
and 015, FR-E710W-008 and 015.
*8 Brake resistor (FR-ABR, MRS, MYS type)
Install a thermal relay to prevent an
overheat and burnout of the brake resistor.
(The brake resistor can not be connected
to the FR-E720-008 and 015, FR-E720S-
008 and 015, FR-E710W-008 and 015.)
Motor
IM
Earth (Ground)
Relay output
Terminal functions vary
by Pr. 192 A,B,C terminal
function selection
Open collector output
Terminal functions vary with
the output terminal assignment
(Pr. 190 and Pr. 191)
(+)
Analog signal output
(0 to 10VDC)
(-)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents