Mitsubishi FREQROL-E700 Manual page 96

Satellite training series
Table of Contents

Advertisement

Function name
Stall
The overcurrent stall
prevention
prevention has been
(overcurrent)
activated.
Stall
The overvoltage stall
prevention
prevention function has
(overvoltage)
been activated.
(This warning is also output
during the regeneration
avoidance operation.)
Warning
Regenerative
The regenerative brake
brake
duty has reached 85%
prealarm*
of the Pr. 70 Special
2
regenerative brake duty
setting or higher.
Electronic
The cumulative value of the
thermal relay
electronic thermal O/L relay
function
has reached 85% of the Pr.
prealarm*
9 Electronic thermal O/L
1
relay setting or higher.
PU stop
has been pressed during
the External operation.
Maintenance
The cumulative
signal output*
energization time has
2
exceeded the maintenance
output timer set value.
Undervoltage The voltage at the main
circuit power has been
lowered.
Fan alarm
The cooling fan is at a
standstill although it is
Minor
required to be operated.
failure
The cooling fan speed has
decelerated.
Description
• Increase or decrease the Pr. 0 Torque boost setting by
1% and check the motor status.
• Set the acceleration/deceleration time longer.
• Reduce the load. Try Advanced magnetic flux vector
control or General-purpose magnetic flux vector
control.
• Check the peripheral devices for faults.
• Adjust the Pr. 13 Starting frequency setting. Change
the Pr. 14 Load pattern selection setting.
• Set the stall prevention operation current in Pr. 22
Stall prevention operation level. (The acceleration/
deceleration time may change.) Increase the stall
prevention operation level with Pr. 22 Stall prevention
operation level, or disable stall prevention with Pr.
156 Stall prevention operation selection. (Operation
at OL occurrence can be selected using Pr. 156 Stall
prevention operation selection.)
Set the deceleration time longer.
• Set the deceleration time longer.
• Check the Pr.30 Regenerative function selection and
Pr. 70 Special regenerative brake duty settings.
• Reduce the load and frequency of operation.
• Set an appropriate value in Pr. 9 Electronic thermal O/
L relay.
Turn the start signal OFF and release with
on the operation panel
Setting "0" in Pr. 503 Maintenance timer erases the
signal.
Investigate the devices on the power supply line such as
the power supply itself.
Check for fan failure. Please contact your sales
representative.
Corrective action
App.2-2