Installation sequence
Electrical connections in the heat pump control...
Installation instructions "External extension H1"
Note
If swimming pool heating is connected to "External extension H1", no hook-up (e.g.
operating mode changeover) can be connected to "External extension H1".
External demand, external mixer "OPEN", operating mode changeover
1X3.13
A
B
1X3.12
A Terminals on PCB 1
B Zero volt N/O contact outside the
heat pump control unit (on site)
Breaking capacity 230 V~; 0.1 A
Required parameters (code to be entered by "Contractor": 5243)
Function
External demand
External mixer "OPEN"
External operating mode
changeover
98
Parameter Ó setting
No parameters need to be set; the set flow tem-
perature for external demand can be specified
(parameter "Set flow ext. demand", see
page 193).
"System definition"
■ "Ext.demand/Miopen" Ó "0" to "7" (see
page 175). Observe parameter "Set flow ext.
demand" (see page 193).
"System definition"
■ "Op. mode change HC" Ó "0" to "10" (see
page 173)
■ "Op. mode change effect" Ó "0" to "3" (see
page 174)
■ "Op. mode change time" Ó "0" to "12" (see
page 174)
(cont.)