Overview of the PCBs and connection options
PCB 2, terminal strip X8
Pos.
Function
End of safety chain
Compressor control via
EEV controller (refrigerant
circuit control)
N/A
Fan control
w¢E
Secondary pump
w¢R
Control of instantaneous
heating water heater,
stage 1
w¢T
Control of the mixer motor,
heating circuit M2, signal
OPEN
w¢Z
Control of the mixer motor,
heating circuit M2, signal
CLOSED
w¢U
Heating circuit pump of the
heating circuit with mixer
M2
Connection and wiring diagrams
Explanation
'Live' in case of fault-free safety
chain
■ Heat demand: Contact closed,
2X8.2 is 'live'
■ If the compressor will not start,
check whether it has been ena-
bled by the EEV controller (own
relay on EEV PCB, see
page 217)
Internal connection
N/A
Internal connection
■ In systems without a heating
water buffer cylinder, no other
heating circuit pump is required
(see terminal 2X7.9)
■ Max. output: 130 W
On-site connection
Accessories
■ Output 10 W
On-site connection
■ 230 V
On-site connection
■ 230 V
On-site connection
■ Max. output: 100 W
On-site connection
(cont.)
Terminals
2X8.1
2X8.1
2X8.2
2X8.3
2X8.4
2X8.5
2X8.7
2X8.8
2X8.9
2X8.10
2X8.11