Control unit diagnostics
Page 1: Binding data
LON diagnosis
SN neuron
7243461
7243459
Netconfig
00
>>
Display
SN neuron
SN foreign
Netconfig
SndHrtBeat
Obj. Status
SKO status
(cont.)
BACK
Explanation
Neuron chip - Viessmann part number
Communication coprocessor - Viessmann part number
Configuration status:
0 "Self binding": Logical linking during installation was
carried out via integral installation program
1 "Tool binding": Logical linking during installation was
carried out via external installation program ("Binding-
tool")
"Send heartbeat":
Currently used time interval in 100 ms to cyclically send
network variables (matching possible via binding tool)
Note
This time interval must be smaller than the receive interval
set at all subscribers; parameter "Receive heartbeat"
Object status
Software communication status:
K LON communication module installed; parameter
"LON module installed" set to "Yes"
F LON communication module processing is enabled.
N Network variable processing is enabled.
A LON communication module recognised, communica-
tion enabled
Troubleshooting