Viessmann Vitocal 350-A Installation And Service Instructions Manual page 95

Type awh-i, awh-o air/water heat pump with electric drive, 400 v~
Hide thumbs Also See for Vitocal 350-A:
Table of Contents

Advertisement

Electrical connections in the heat pump control...
Appliance
Vitosolic 200
Motorised two-way valve and
cylinder primary pump (DHW
heating with primary store sys-
tem; both components to
2X8.12)
Instantaneous heating water heater (accessory)
Connection
Installation instructions
Instantaneous heating water
heater for the Vitocal 350-A, type
AWH-I, AWH-O (accessory).
Required parameters:
Parameter Ó setting
"Electric heater"
■ "Inst. heating water heater" Ó "Yes"
Power-OFF
The supply voltage to the relevant components (subject to power supply utility) is
switched off by the power-OFF contact signal.
1X3.7
A
B
1X3.6
A Terminals on PCB 1
B Zero volt N/C contact
Breaking capacity 230 V~, 0.5A,
remove jumper when making this
connection
Connection
Required parameters:
Parameter Ó setting
3X1.25Ó aVG
"System definition"
■ "Vitosolic type" Ó "2"
3X2.25Ó aVG
2X8.12
"System definition"
1X2.N
■ "System diagram" Ó with
1X1.?
DHW heating
(see page 50)
Installation instructions
Control module for instantaneous
heating water heater (acces-
sory).
Contact open:
Contact closed:
Note
■ No parameters need to be set.
■ The compressor is switched off as
soon as the contact opens.
■ For the instantaneous heating water
heater, the stages to be switched off
can be selected. See parameter
"Stage at power-OFF" (790A) on
page 190.
Installation sequence
(cont.)
Power-OFF ena-
bled
Power-OFF disa-
bled