Troubleshooting
Control unit diagnostics
Diagnosis overview
Diag. HP module
[ - ] :
0100 4000 0101
Tsh, Tc
[ °C ] :
pmop
[ bara ] :
Ts, Tc
[ °C ] :
ps, pc
[ bara ] :
T1
[ °C ] :
x, P
[ % ] :
00 : 00000001
Err
[ - ] :
2
T/P
Displays
Display
Explanation
I [–]
Information index (commands, status, versions):
12 digits, 4 different codes possible at each position, hexadecimal dis-
play; observe the subsequent display system
Tsh, Tc [°C] Tsh: Set superheating temperature
Tc: Set hot gas temperature for start of the vapour injection (EVI)
Pmop
Max. suction gas pressure ("maximum operating pressure")
[bara]
Max. evaporator operating pressure
Ts, Tc [°C]
Ts: Actual suction gas temperature
Tc: Actual condensation temperature
Ps [bara]
Actual suction gas pressure
Pc [bara]
Actual condensation pressure
TI [°C]
Actual LPG temperature
x, P [%]
x: Last EEV position
P: Most recent set value default for the compressor output, calculated
by heat pump control unit from current heat demand in the secondary
circuit
Err [–]
Fault index (component, message):
10 digits, 4 different codes possible at each position, hexadecimal dis-
play; observe the subsequent display system
152
(cont.)
1
3.0,
68.0
6.6
19.8,
63.9
6.2,
14.1
28.8
100
, - - -
H
BACK
Note
■ The information displayed in "Diag.
HP module" is independent of the
fault codes in the heat pump control
unit.
■ The diagnosis of compressor stage 1
or 2 is called up with "1" or "2". The
diagnosis for compressor stage 2 has
no function.