Commissioning, inspection, maintenance
Further details regarding the individual steps
Carrying out subscriber check
In conjunction with LON.
Communication with the system devices connected to the fault manager is tested
with a subscriber check.
Preconditions:
■ The heat pump control unit must be
programmed as the fault manager
("Fault manager")
■ The LON subscriber number must be
programmed in all control units (see
page 128)
■ The LON subscriber list in the fault
manager must be up to date (see
page 129)
Press the following keys:
1. To log on as "Contractor", see
page 168.
2. "Device settings".
3. "Contractor level".
4. "LON subscriber" for subscriber
list.
5. y/x for the required sub-
scriber.
Instructing the system user
The system installer must hand the operating instructions to the system user and
instruct him/her in the operation of the system.
130
(cont.)
6. "WINK"
Check is enabled.
Displaying:
■ "check": Subscriber
check runs; "LON –
WINK" flashes for
30 s on the display of
the selected sub-
scriber (if installed).
■ "check OK"
■ "check NOK": No
communication
between the two devi-
ces. Check the LON
connection and
codes; restart sub-
scriber check.
7. Repeat points 5 and 6 to check further
subscribers.
8. "BACK"
to exit the menu.