Chapter 4
Register
Function name
No.
142Ah
Frequency arrival setting for accel.
142Bh
142Ch
Frequency arrival setting for decel.
142Dh
142Eh
PID deviation level setting
142Fh
Frequency arrival setting for
1430h
acceleration (2)
1431h
Frequency arrival setting for
1432h
deceleration (2)
1433h to
(Reserved)
1437h
1438h
Maximum PID feedback data
1439h
Minimum PID feedback data
143Ah
(Reserved)
Over-torque (forward-driving) level
143Bh
setting
Over-torque (reverse regenerating)
143Ch
level setting
Over-torque (reverse driving) level
143Dh
setting
Over-torque (forward regenerating)
143Eh
level setting
143Fh
(Reserved)
1440h
(Reserved)
Electronic thermal warning level
1441h
setting
1442h
Alarm code output
1443h
Zero speed detection level
1444h
Heat sink overheat warning level
1445h to
(Reserved)
144Ah
144Bh
Communication speed selection
144Ch
Node allocation
144Dh
Communication data length selection
144Eh
Communication parity selection
144Fh
Communication stop bit selection
Selection of the operation after
1450h
communication error
1451h
Communication timeout limit
1452h
Communication wait time
1453h
Communication mode selection
1454h
(Reserved)
1455h
[O] input span calibration
1456h
[OI] input span calibration
1457h
[O2] input span calibration
1458h
(Reserved)
1459h
Thermistor input tuning
145Ah to
(Reserved)
145Eh
145Fh
Debug mode enable
1460h to
(Reserved)
1468h
1469h
Up/Down memory mode selection
146Ah
Reset mode selection
146Bh
Restart mode after reset
146Ch
(Reserved)
146Dh
FM gain adjustment
146Eh
AM gain adjustment
146Fh
AMI gain adjustment
(Note) <>indicate the setting range of 75 to 150kW
Function code
R/W
Monitoring and setting items Data resolution
C042 (high)
R/W
0 to 40000
C042 (low)
R/W
C043 (high)
R/W
0 to 40000
C043 (low)
R/W
C044
R/W 0 to 1000
C045 (high)
R/W
0 to 40000
C045 (low)
R/W
C046 (high)
R/W
0 to 40000
C046 (low)
R/W
-
-
Inaccessible
C052
R/W 0 to 1000
C053
R/W 0 to 1000
R/W
C055
R/W 0 to 200 <0 to 180>(CT), 0 to 150(VT)
C056
R/W 0 to 200 <0 to 180>(CT), 0 to 150(VT)
C057
R/W 0 to 200 <0 to 180>(CT), 0 to 150(VT)
C058
R/W 0 to 200 <0 to 180>(CT), 0 to 150(VT)
-
-
Inaccessible
-
-
Inaccessible
C061
R/W 0 to 100
C062
R/W 0 (disabling alarm output), 1 (3 bits), 2 (4 bits)
C063
R/W 0 to 10000
C064
R/W 0 to 200
-
-
Inaccessible
2 (loopback test), 3 (2.4kbps), 4 (4.8k bps),
5 (9.6kbps), 6(19.2kbps), 7(38.4kbps), 8(57.6kbps),
C071
R/W
9(76.8kbps)
C072
R/W 1. to 247.
C073
R/W 7 (7 bits), 8 (8 bits)
C074
R/W 00 (no parity), 01 (even parity), 02 (odd parity)
C075
R/W 1 (1 bit), 2 (2 bits)
0 (tripping), 1 (tripping after decelerating and
stopping the motor), 2 (ignoring errors), 3 (stopping
C076
R/W
the motor after free-running), 4 (decelerating and
stopping the motor)
C077
R/W 0 to 9999
C078
R/W 0 to 1000
C079
R/W 0 (ASCII), 1 (Modbus-RTU)
-
-
Inaccessible
C081
R/W 0 to 65530
C082
R/W 0 to 65530
C083
R/W 0 to 65530
-
-
Inaccessible
C085
R/W 0 to 10000
-
-
Inaccessible
C091
R
0/1
-
-
Inaccessible
0 (not storing the frequency data), 1 (storing the
C101
R/W
frequency data)
0 (resetting the trip when RS is on), 1 (resetting the
trip when RS is off), 2 (enabling resetting only upon
C102
R/W
tripping [resetting when RS is on]), 3(resetting only
trip)
0 (starting with 0 Hz), 1 (starting with matching
C103
R/W
frequency), 2 (restarting with active matching
frequency)
-
-
Inaccessible
C105
R/W 50 to 200
C106
R/W 50 to 200
C107
R/W 50 to 200
4-157
Explanation of Functions
,
10(115.2kbps)
Data
resolution
0.01 [Hz]
0.01 [Hz]
0.1 [%]
0.01 [Hz]
0.01 [Hz]
-
0.1 [%]
0.1 [%]
-
1 [%]
1 [%]
1 [%]
1 [%]
-
-
1 [%]
-
0.01 [Hz]
1 [℃]
-
-
-
-
-
-
-
0.01 [sec.]
1 [msec.]
-
-
1
1
1
-
0.1
-
-
-
-
-
-
-
1 [%]
1 [%]
1 [%]

Advertisement