Hitachi SJ700D-004L Instruction Manual page 197

Sj700d-3 series
Hide thumbs Also See for SJ700D-004L:
Table of Contents

Advertisement

Chapter 4
(xii) 0B command: This command recalculates the constants set in the inverter.
This command must be issued when the base frequency or the setting of parameter "H***" has been changed for the
RS485 communication.
- Transmission frame
Frame format
STX
Station No.
STX
Control code (Start of TeXt)
Station number of control-target
Station No.
inverter
Command
Command to be transmitted
BCC
Block check code
CR
Control code (Carriage Return)
- Response frame
Positive response: See Item (2)-(i) of this section.
Negative response: See Item (2)-(ii) of this section.
Command
BCC
Description
Explanation of Functions
CR
Data size
1 byte
STX (0x02)
2 bytes
01 to 32
2 bytes
0B
XOR of the items from "Station No." to "Data." See
2 bytes
Item (3) of this section.
1 byte
CR (0x0D)
4-126
Setting