6.3.3

Configuring communication to the control

Configuring the communication using SIMATIC S7 control
You have the following options, if the inverter is not included in the hardware library:
● Install the most up to date STARTER version
● Install the GSDML of the inverter using "Tools/Install GSDML file" in HW Config.
Additional information on this topic is provided in the "Fieldbuses" Function Manual, also see
Manuals for your inverter (Page 387).
Configuring the communication using a non-Siemens control
1. Import the device file (GSDML) of the inverter into the engineering tool for your control
system.
2. Configure the communication.
Configure communication with STARTER
STARTER provides a screen form to set the communication with the control system.
Open the dialog screen form "Control_Unit/Communication/Commissioning interface" and
activate the "Configure IP interfaces" tab
● Set the DHCP mode to 0 (factory setting).
● Enter the device name, address, gateway and the address for the subnet mask.
● In the Activation field select "[2] Save and activate configuration".
● To activate the settings, you must switch off the inverter power supply and then switch on
again.
You can also enter or read out data using the expert list. You can find the corresponding
parameters in the number range r8909 ... p8925
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
Adapt fieldbus configuration
6.3 Communication via PROFINET
107