Safety Warnings Summary

NOTE: This is a summary of safety warnings. For a complete list of warnings, including
translations, see the Getting Started Guide for your router at
http://www.juniper.net/techpubs/
WARNING: Certain ports on the router are designed for use as intrabuilding
(within-the-building) interfaces only (Type 2 or Type 4 ports as described in
GR-1089-CORE
cabling. To comply with NEBS requirements and protect against lightening surges
and commercial power disturbances, the intrabuilding ports must not be metallically
connected to interfaces that connect to the OSP or its wiring. The intrabuilding ports
on the router are suitable for connection to intrabuilding or unexposed wiring or
cabling only. The addition of primary protectors is not sufficient protection for
connecting these interfaces metallically to OSP wiring.
CAUTION: To comply with intrabuilding lightning and surge requirements,
intrabuilding wiring must be shielded, and the shield for the wiring must be grounded
at both ends.
CAUTION: Before removing or installing components of a router, attach an ESD strap
to an ESD point and place the other end of the strap around your bare wrist. Failure
to use an ESD strap could result in damage to the router.
CAUTION: For routers with AC power supplies, an external surge protective device
(SPD) must be used at the AC power source.
18
Safety Warnings Summary
.
, Issue 4) and require isolation from the exposed outside plant (OSP)