Certification
Test
IEEE C37.90
IEEE C37.90.1
IEEE C37.90.2
IEEE C37.90.3

Environmental Type Tests

Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-3
MIL-STD-810G
IEC 61373
50
Description
HV Impulse
Dielectric Strength
Fast Transient
Oscillatory
Radiated RFI
ESD
Description
Cold Temperature
Dry Heat
Humidity (Damp Heat, Cyclic)
Vibration
Shock
Bump
Seismic
Altitude
Long Life
Shock
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Signal ports
DC Power Ports
AC Power Ports
Enclosure ports
Enclosure Contact
Enclosure Air
Test Ad
Test Bd
Test Db
95% (non-condensing), 55 °C (131 °F), 6 cycles
12192 m (40000 ft) @ 40 °C x 90 minutes
RUGGEDCOM RX1501
Installation Guide
Test Levels
5 kV (Failsafe Relay Output)
5 kV
2 kVAC
1.5 kVDC
2 kVAC
+/- 4 kV @ 2.5 kHz
+/- 4 kV
2.5 kV common mode @1MHz
2.5 kV common, 1 kV
differential mode @ 1 MHz
35 V/m
+/-2 kV, +/-4 kV, +/- 8 kV
+/-4 kV, +/-8 kV, +/-15 kV
Test Levels
-40 °C (-40 °F), 16 Hours
85 °C (185 °F), 16 Hours
Level 2 (2 g @ 10-150 Hz)
Level 2 (30 g @ 11 mS)
Level 1 (10 g @ 16 mS)
Level 2 (Method A)
Category 1 Class B
EMI and Environmental Type Tests