Muting state can be also released when the sensor enters lockout.
 Installation standard for muting sensors
•Set the muting sensors so that they can detect all of the passing detection objects (palettes,
automobiles, etc.). Do not install in a position so that only the front or rear end of the detection object
is detected.
•Set the muting sensors so that they detect the objects even when they are loaded on palettes or other
transport devices.
•Also, install the F3SJ-B and muting sensors so that each object passes through all muting sensors
before the next object arrives at the first muting sensor. Also, install all F3SJ-Bs and muting sensors
so that no person is able to accidentally enter the hazardous zone while the muting function is
enabled.
•If objects' speeds can vary, the allocation of muting sensors must be taken into consideration.
•Install muting sensors so that they can distinguish between the object that is being allowed to be
passed through the detection zone and a person.
System Configuration and Functions
Value
0.1 s
Minimum time difference between muting inputs 1 and 2.
If the time difference between muting inputs 1 and 2 is smaller
than this value, a muting error occurs.
3 s
Maximum time difference between muting inputs 1 and 2.
If the time difference between muting inputs 1 and 2 is larger than
this value, a muting error occurs.
60 s
This is the muting function continuation time.
If muting state exceeds this time, the function is canceled.
0.1 s
Maximum muting input time with allowable waveform cracks in
muting input 1 and 2.