6 Configuration and Settings
6.2 Configuring the SINAMICS G drive
No.
Action
14.
Open "Inputs/outputs" in the
tree
Click on the magenta
colored field next to digital
input 0
Remove all checkmarks in
the "Control_Unit, ....D0
(Kl.5)" window and then
close this window with OK
Repeat this for DI1 to DI5
15.
If the "PROFIsafe Telegram 900"
frame is configured, please
proceed with step 16.
If the "PROFIsafe Telegram 30"
frame is configured, please
proceed with step 24.
16.
Open "Safety Integrated" in
the tree.
Select "Extended functions
via PROFIsafe".
Confirm that a PROFIsafe
message frame has been
created.
17.
Open the "Safety inputs" dialog.
SINAMICS G120C at S7-300/400F-DP
Beitrags-ID: 60441457,
V2.2,
DI 0 to 5 shall be used as fail-safe inputs, however, they
retain their function as standard inputs. Controlling FDI 0
(Kl. 5+6) would therefore also trigger those functions which
were configured on DI0 (Kl. 5) and DI1 (Kl. 6) (Jog Bit 0/1).
To prevent this, the functions of the standard inputs are
deleted.
11/2014
Remarks