6 Configuration and Settings
6.2 Configuring the SINAMICS G drive
No.
Action
12.
Run the wizard and enter the
data you need.
If you have no specific
requirements, use the respective
default values, apart from the
following exceptions
Ensure that the field bus
(FieldBus With data Set
Change) is selected in the
"Defaults of the
setpoint/command sources"
step.
In the "Motor" step you enter
the data of the connected
motor.
13.
After the wizard has been run
through completely, double-click
on "Communication >
PROFIBUS" in the tree,
select one of the "Receive"
or "Send direction" tabs
select "PROFIsafe telegram"
900 or 30
select "Siemens message
frame 352, PZD 6/6)".
Note:
It is decisive here that the same
message frames is selected as
for the hardware configuration in
STEP 7.
SINAMICS G120C at S7-300/400F-DP
Beitrags-ID: 60441457,
V2.2,
11/2014
Remarks
78