Commissioning The Sm 431; Ai 16 X 16 Bit - Siemens SIMATIC S7-400 Reference Manual

Automation system module data
Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Analog modules
5.23 Analog input module SM 431; AI 16 x 16 Bit (6ES7431-7QH00-0AB0)
5.23.2

Commissioning the SM 431; AI 16 x 16 Bit

Setting the operating mode
You set the mode of operation of the SM 431; AI 16 x 16 Bit by means of measuring range
modules on the module and in STEP 7.
Measuring range modules
A measuring range module of the module matches two channels and one resistance channel
to each type of sensor. Reposition the measuring range modules to suit the measuring method
and range. The steps you have to perform to do this are described in detail in the respective
section.
For an overview of the settings of specific measuring methods and ranges, refer to the
corresponding table in the section "Measuring methods and measuring ranges of SM 431;
AI 16 x 16 Bit". The necessary settings are also shown on the label attached to the module.
Parameters
You will find a description of the general procedure for assigning parameters to analog modules
in the respective sections.
The table below provides an overview of configurable parameters, including defaults.
Table 5-61
Parameters of the SM 431; AI 16 x 16 Bit
Parameters
Enable
● Diagnostic interrupt
1
● Hardware interrupt
1
● Destination CPU for interrupt
Hardware interrupt trigger
● End of scan cycle reached at input Yes/no
● High limit
● Low limit
Diagnostics
● Wire break
● Reference channel error
● Underflow
● Overflow
● Short-circuit to M
Measurement
284
Value range
Yes/no
Yes/no
1 to 4
32511 to - 32512
-32512 to 32511
Yes/no
Yes/no
Yes/no
Yes/no
Yes/no
Default
Parameter
2
type
No
Dynamic
No
-
Static
No
Static
-
Dynamic
No
Static
No
No
No
No
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
Scope
Module
Module
Channel
Channel
Channel

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents